| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2017-6865 | 1 Siemens | 16 Pcs 7, Primary Setup Tool, Security Configuration Tool and 13 more | 2025-04-20 | N/A |
| A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover. | ||||
| CVE-2017-2685 | 1 Siemens | 3 Sinumerik Integrate Access Mymachine\/ethernet, Sinumerik Integrate Operate Client, Sinumerik Operate | 2025-04-20 | N/A |
| Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. | ||||
| CVE-2017-12734 | 1 Siemens | 2 Logo\!8 Bm Fs-05, Logo\!8 Bm Fs-05 Firmware | 2025-04-20 | 7.5 High |
| A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V1.81.2). An attacker with network access to the integrated web server on port 80/tcp could obtain the session ID of an active user session. A user must be logged in to the web interface. Siemens recommends to use the integrated webserver on port 80/tcp only in trusted networks. | ||||
| CVE-2017-12069 | 2 Ocpfoundation, Siemens | 4 Local Discovery Server, Ua .net, Simatic Pcs7 and 1 more | 2025-04-20 | N/A |
| An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker. | ||||
| CVE-2017-2681 | 1 Siemens | 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more | 2025-04-20 | 6.5 Medium |
| Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. | ||||
| CVE-2015-7977 | 9 Canonical, Debian, Fedoraproject and 6 more | 13 Ubuntu Linux, Debian Linux, Fedora and 10 more | 2025-04-20 | 5.9 Medium |
| ntpd in NTP before 4.2.8p6 and 4.3.x before 4.3.90 allows remote attackers to cause a denial of service (NULL pointer dereference) via a ntpdc reslist command. | ||||
| CVE-2016-7987 | 1 Siemens | 8 Eta2 Firmware, Eta4 Firmware, Sicam Ak and 5 more | 2025-04-20 | N/A |
| An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability. | ||||
| CVE-2017-2687 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
| Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability in the integrated web server at port 10000/TCP which is prone to reflected Cross-Site Scripting attacks if an unsuspecting user is induced to click on a malicious link. | ||||
| CVE-2017-12739 | 1 Siemens | 2 Sm-2556, Sm-2556 Firmware | 2025-04-20 | N/A |
| An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to execute arbitrary code on the affected device. | ||||
| CVE-2017-9946 | 1 Siemens | 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more | 2025-04-20 | 7.5 High |
| A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. An attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device. | ||||
| CVE-2017-9945 | 1 Siemens | 2 7km Pac Switched Ethernet Profinet Expansion Module, 7km Pac Switched Ethernet Profinet Expansion Module Firmware | 2025-04-20 | N/A |
| In the Siemens 7KM PAC Switched Ethernet PROFINET expansion module (All versions < V2.1.3), a Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover. | ||||
| CVE-2017-9947 | 1 Siemens | 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more | 2025-04-20 | 5.3 Medium |
| A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices. | ||||
| CVE-2017-12741 | 1 Siemens | 76 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200p and 73 more | 2025-04-20 | 7.5 High |
| Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. | ||||
| CVE-2016-8566 | 1 Siemens | 1 Sicam Pas\/pqs | 2025-04-20 | 7.8 High |
| An issue was discovered in Siemens SICAM PAS before 8.00. Because of Storing Passwords in a Recoverable Format, an authenticated local attacker with certain privileges could possibly reconstruct the passwords of users for accessing the database. | ||||
| CVE-2017-2686 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
| Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability that could allow an authenticated user to read arbitrary files through the web interface at port 10000/TCP and access sensitive information. | ||||
| CVE-2017-6458 | 4 Apple, Hpe, Ntp and 1 more | 5 Mac Os X, Hpux-ntp, Ntp and 2 more | 2025-04-20 | 8.8 High |
| Multiple buffer overflows in the ctl_put* functions in NTP before 4.2.8p10 and 4.3.x before 4.3.94 allow remote authenticated users to have unspecified impact via a long variable. | ||||
| CVE-2015-7973 | 5 Canonical, Freebsd, Netapp and 2 more | 9 Ubuntu Linux, Freebsd, Clustered Data Ontap and 6 more | 2025-04-20 | 6.5 Medium |
| NTP before 4.2.8p6 and 4.3.x before 4.3.90, when configured in broadcast mode, allows man-in-the-middle attackers to conduct replay attacks by sniffing the network. | ||||
| CVE-2017-2680 | 1 Siemens | 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more | 2025-04-20 | 6.5 Medium |
| Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. | ||||
| CVE-2016-2518 | 7 Debian, Freebsd, Netapp and 4 more | 20 Debian Linux, Freebsd, Clustered Data Ontap and 17 more | 2025-04-20 | 5.3 Medium |
| The MATCH_ASSOC function in NTP before version 4.2.8p9 and 4.3.x before 4.3.92 allows remote attackers to cause an out-of-bounds reference via an addpeer request with a large hmode value. | ||||
| CVE-2017-6871 | 1 Siemens | 2 Simatic Wincc Sm\@rtclient, Simatic Wincc Sm\@rtclient Lite | 2025-04-20 | N/A |
| A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2) and SIMATIC WinCC Sm@rtClient for Android Lite (All versions before V1.0.2.2). An attacker with physical access to an unlocked mobile device, that has the affected app running, could bypass the app's authentication mechanism under certain conditions. | ||||