CVE-2011-4055 1 Siemens 1 Tecnomatix Factorylink 2025-04-11 N/A
Buffer overflow in the WebClient ActiveX control in Siemens Tecnomatix FactoryLink 6.6.1 (aka 6.6 SP1), 7.5.217 (aka 7.5 SP2), and 8.0.2.54 allows remote attackers to execute arbitrary code via a long string in a parameter associated with the location URL.
CVE-2011-4515 1 Siemens 1 Wincc Tia Portal 2025-04-11 N/A
Siemens WinCC (TIA Portal) 11 uses a reversible algorithm for storing HMI web-application passwords in world-readable and world-writable files, which allows local users to obtain sensitive information by leveraging (1) physical access or (2) Sm@rt Server access.
CVE-2013-0670 1 Siemens 1 Wincc Tia Portal 2025-04-11 N/A
CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL.
CVE-2013-5944 1 Siemens 3 Scalance X-200, Scalance X-200 Series Firmware, Scalance X-200irt 2025-04-11 N/A
The integrated web server on Siemens SCALANCE X-200 switches with firmware before 4.5.0 and X-200IRT switches with firmware before 5.1.0 does not properly enforce authentication requirements, which allows remote attackers to perform administrative actions via requests to the management interface.
CVE-2014-1966 1 Siemens 3 Ruggedcom Rs950g, Ruggedcom Rsg2488, Ruggedcom Rugged Operating System 2025-04-11 N/A
The SNMP implementation in Siemens RuggedCom ROS before 3.11, ROS 3.11 for RS950G, ROS 3.12 before 3.12.4, and ROS 4.0 for RSG2488 allows remote attackers to cause a denial of service (device outage) via crafted packets.
CVE-2012-2596 1 Siemens 1 Wincc 2025-04-11 N/A
The XPath functionality in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 does not properly handle special characters in parameters, which allows remote authenticated users to read or modify settings via a crafted URL, related to an "XML injection" attack.
CVE-2012-4698 1 Siemens 4 Ros, Rox I Os, Rox Ii Os and 1 more 2025-04-11 N/A
Siemens RuggedCom Rugged Operating System (ROS) before 3.12, ROX I OS through 1.14.5, ROX II OS through 2.3.0, and RuggedMax OS through 4.2.1.4621.22 use hardcoded private keys for SSL and SSH communication, which makes it easier for man-in-the-middle attackers to spoof servers and decrypt network traffic by leveraging the availability of these keys within ROS files at all customer installations.
CVE-2012-2595 1 Siemens 1 Wincc 2025-04-11 N/A
Multiple cross-site scripting (XSS) vulnerabilities in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 allow remote attackers to inject arbitrary web script or HTML via vectors involving special characters in parameters.
CVE-2011-4531 1 Siemens 1 Automation License Manager 2025-04-11 N/A
Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allows remote attackers to cause a denial of service (NULL pointer dereference and daemon crash) via crafted content in a (1) get_target_ocx_param or (2) send_target_ocx_param command.
CVE-2012-3032 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
SQL injection vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to execute arbitrary SQL commands via a crafted SOAP message.
CVE-2012-3031 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header.
CVE-2012-3030 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request.
CVE-2012-3017 1 Siemens 4 Simatic S7-400 Cpu 414-3 Pn\/dp, Simatic S7-400 Cpu 416-3 Pn\/dp, Simatic S7-400 Cpu 416f-3 Pn\/dp and 1 more 2025-04-11 N/A
Siemens SIMATIC S7-400 PN CPU devices with firmware 5.x allow remote attackers to cause a denial of service (defect-mode transition and service outage) via (1) malformed HTTP traffic or (2) malformed IP packets.
CVE-2012-3028 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service.
CVE-2012-3020 1 Siemens 2 Synco Ozw Web Server, Synco Ozw Web Server Firmware 2025-04-11 N/A
The Siemens Synco OZW Web Server devices OZW672.*, OZW772.*, and OZW775 with firmware before 4 have an unspecified default password, which makes it easier for remote attackers to obtain administrative access via a network session.
CVE-2013-0700 1 Siemens 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more 2025-04-11 N/A
Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).
CVE-2013-3958 1 Siemens 2 Simatic Pcs7, Wincc 2025-04-11 N/A
The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request.
CVE-2013-6920 1 Siemens 14 Sinamics G110, Sinamics G110d, Sinamics G120 and 11 more 2025-04-11 N/A
Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23.
CVE-2012-3009 1 Siemens 1 Comos 2025-04-11 N/A
Siemens COMOS before 9.1 Patch 413, 9.2 before Update 03 Patch 023, and 10.0 before Patch 005 allows remote authenticated users to obtain database administrative access via unspecified method calls.
CVE-2012-3003 1 Siemens 1 Wincc 2025-04-11 N/A
Open redirect vulnerability in an unspecified web application in Siemens WinCC 7.0 SP3 before Update 2 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via a URL in a GET request.