Filtered by vendor Schneider-electric
Subscriptions
Total
789 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2017-9629 | 1 Schneider-electric | 1 Wonderware Archestra Logger | 2025-04-20 | 9.8 Critical |
| A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account. | ||||
| CVE-2017-7574 | 1 Schneider-electric | 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine | 2025-04-20 | 9.8 Critical |
| Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. | ||||
| CVE-2020-25178 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 7.5 High |
| ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. | ||||
| CVE-2020-25182 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 6.7 Medium |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. | ||||
| CVE-2020-25176 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 9.1 Critical |
| Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution. | ||||
| CVE-2020-25184 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 7.8 High |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure. | ||||
| CVE-2020-25180 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 5.3 Medium |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device. | ||||
| CVE-2015-6485 | 1 Schneider-electric | 8 Sage 1410, Sage 1430, Sage 1450 and 5 more | 2025-04-12 | N/A |
| Schneider Electric Telvent Sage 2300 RTUs with firmware before C3413-500-S01, and LANDAC II-2, Sage 1410, Sage 1430, Sage 1450, Sage 2400, and Sage 3030M RTUs with firmware before C3414-500-S02J2, allow remote attackers to obtain sensitive information from device memory by reading a padding field of an Ethernet packet. | ||||
| CVE-2016-2291 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 6.5 Medium |
| Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allow remote attackers to execute arbitrary code or cause a denial of service (out-of-bounds read) via unspecified vectors. | ||||
| CVE-2014-9206 | 1 Schneider-electric | 1 Device Type Manager | 2025-04-12 | N/A |
| Stack-based buffer overflow in Device Type Manager (DTM) 3.1.6 and earlier for Schneider Electric Invensys SRD Control Valve Positioner devices 960 and 991 allows local users to gain privileges via a malformed DLL file. | ||||
| CVE-2016-2278 | 1 Schneider-electric | 4 Struxureware Building Operations Automation Server As, Struxureware Building Operations Automation Server As-p, Struxureware Building Operations Automation Server As-p Firmware and 1 more | 2025-04-12 | N/A |
| Schneider Electric Struxureware Building Operations Automation Server AS 1.7 and earlier and AS-P 1.7 and earlier allows remote authenticated administrators to execute arbitrary OS commands by defeating an msh (aka Minimal Shell) protection mechanism. | ||||
| CVE-2015-3977 | 1 Schneider-electric | 1 Imt25 Magnetic Flow Dtm | 2025-04-12 | N/A |
| Buffer overflow in Schneider Electric IMT25 Magnetic Flow DTM before 1.500.004 for the HART Protocol allows remote authenticated users to execute arbitrary code or cause a denial of service (memory corruption) via a crafted HART reply. | ||||
| CVE-2015-7921 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 9.1 Critical |
| The FTP server in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 has hardcoded credentials, which makes it easier for remote attackers to bypass authentication by leveraging knowledge of these credentials. | ||||
| CVE-2016-2290 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 8.8 High |
| Heap-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors. | ||||
| CVE-2015-3940 | 1 Schneider-electric | 1 Wonderware System Platform 2014 | 2025-04-12 | N/A |
| Untrusted search path vulnerability in Schneider Electric Wonderware System Platform before 2014 R2 Patch 01 allows local users to gain privileges via a Trojan horse DLL in an unspecified directory. | ||||
| CVE-2015-0999 | 2 Aveva, Schneider-electric | 2 Aveva Edge, Wonderware Intouch 2014 | 2025-04-12 | N/A |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 store cleartext OPC User credentials in a configuration file, which allows local users to obtain sensitive information by reading this file. | ||||
| CVE-2015-0997 | 2 Aveva, Schneider-electric | 2 Aveva Edge, Wonderware Intouch 2014 | 2025-04-12 | N/A |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 provide an HMI user interface that lists all valid usernames, which makes it easier for remote attackers to obtain access via a brute-force password-guessing attack. | ||||
| CVE-2015-0998 | 2 Aveva, Schneider-electric | 2 Aveva Edge, Wonderware Intouch 2014 | 2025-04-12 | N/A |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 transmit cleartext credentials, which allows remote attackers to obtain sensitive information by sniffing the network. | ||||
| CVE-2016-2292 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 6.5 Medium |
| Stack-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors. | ||||
| CVE-2016-4520 | 1 Schneider-electric | 1 Pelco Digital Sentry Video Management System Firmware | 2025-04-12 | N/A |
| Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors. | ||||